WILO STRATOS

WILO STRATOS

Application
Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulation systems. 
 
Special features/product advantages
  • Energy savings through greater system efficiency with the Q-Limit function (volume flow limiter)
  • Improved Energy Efficiency Index (EEI) ≤0.20 for all single pumps.
  • Optimised display for better readability and operation
  • Space-saving installation due to compact design and location-dependent LC display
  • Modular concept for connection of all conventional bus systems (e.g. Modbus, BACnet, CAN, LON and PLR)
  • Tried and tested quality and reliability
Technical data
  • Energy efficiency index (EEI) ≤ 0.20
  • Permissible temperature range ‐-10°C to +110°C
  • Mains connection 1~230 V, 50/60 Hz
  • Protection class IP X4D
  • Screwed connection or flange connection (depending on type) Rp 1 to DN 100
  • Max. operating pressure, standard version: 6/10 bar or 6 bar (special version: 10 bar or 16 bar)

 

WILO STRATOS D

WILO STRATOS D

Application
Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulation systems 
 
Special features/product advantages
  • Energy savings through greater system efficiency with the Q-Limit function (volume flow limiter)
  • Improved Energy Efficiency Index (EEI) ≤0.23 for all double pumps.
  • Optimised display for better readability and operation
  • Space-saving installation due to compact design and location-dependent LC display
  • Modular concept for connection of all conventional bus systems (e.g. Modbus, BACnet, CAN, LON and PLR)
  • Dual pump management via retrofittable IF-Modules:
  • Tried and tested quality and reliability
Technical data
  • Energy efficiency index (EEI) ≤ 0.27
  • Permissible temperature range ‐-10°C to +110°C
  • Mains connection 1~230 V, 50/60 HzProtection class IP X4D
  • Flange connection DN 32 to DN 80
  • Max. operating pressure, standard version: 6/10 bar or 6 bar (special version: 10 bar or 16 bar)

 

WILO YONOS PICO

WILO YONOS PICO

Application
All hot water heating systems, air-conditioning applications, industrial circulation systems.
 
Special features/product advantages
  • LED display for adjusting the setpoint in 0.1 m increments and showing effective consumption
  • Tool-free electrical connection using the Wilo-Connector
  • Unique pump venting function
  • Simple adjustment when replacing an uncontrolled standard pump with preselectable speed stages, e.g. Wilo-Star-RS
  • Very high starting torque for reliable starting
Technical data
  • Energy efficiency index (EEI) ≤ 0.20
  • Fluid temperature -10°C to +95°C
  • Mains connection 1~230 V, 50 Hz
  • Protection class IP X2 D
  • Threaded connection Rp ½, Rp 1 and Rp 1¼
  • Max. operating pressure 6 bar

 

WILO STRATOS PICO

WILO STRATOS PICO

Application
All hot water heating systems, air-conditioning applications, industrial circulation systems. 
 
Special features/product advantages
  • Can be used in heating and air-conditioning systems from +2 °C to +110°C
  • Only 3 watts minimum power consumption
  • Displays the current power consumption or the current flow and cumulated kWhWilo-Connector
  • Additional functions: Dynamic Adapt, venting routine, setback operation, key lock and Reset function
Technical data
  • Energy efficiency index (EEI) ≤ 0.20
  • Fluid temperature +2 °C to +110 °C
  • Mains connection 1~230 V, 50 Hz
  • Protection class IP X4D
  • Threaded connection Rp ½, Rp 1 and Rp 1¼
  • Max. operating pressure 10 bar

 

WILO YONOS ECO -BMS

WILO YONOS ECO -BMS

Application
Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulation systems
 
Special features/product advantages
  • Potential-free collective fault signal contact (SSM) for connection to external monitoring units (e.g. building automation) and control input 0-10 V
  • Control cable (4-wire, 1.5 m) for SSM connection and 0-10 V
  • Wilo-Connector
  • Thermal insulation as standard
  • Pump housing with cataphoretic (KTL) coating protects against corrosion due to condensation formation
Technical data
  • Energy efficiency index (EEI) ≤ 0.20
  • Fluid temperature -10 °C to +110 °C (at max. ambient temperature +25 °C)
  • Mains connection 1~230 V, 50/60 Hz;
  • Protection class IP 44
  • Threaded connection Rp 1 and Rp 1¼
  • Max. operating pressure 10 bar
WILO VEROLINE IP-Z

WILO VEROLINE IP-Z

Application
For pumping drinking water, cold and hot water (in accordance with VDI 2035) without abrasive substances, in heating, cold water and cooling water systems
 
Special features/product advantages
  • High resistance to corrosive fluids due to stainless steel housing and Noryl impeller
  • Wide range of applications due to suitability for water hardness up to 5 mmol/l (28 °dH)
  • All plastic parts that come into contact with the fluid fulfil KTW recommendations
Technical data
  • Permissible temperature range
  • Drinking water up to 5 mmol/l (28 °dH): max. +65 °C, in short-term operation (2 h) up to +110 °C
  • Heating water: -8 °C to +110 ° C)
  • Mains connection 1~230 V, 50 Hz or 3~230/400 V, 50 Hz
  • Protection class IP 44 motor, IP 54 terminal box
  • Nominal diameter Rp 1
  • Max. operating pressure 10 bar

 

WILO VEROLINE IPS

WILO VEROLINE IPS

Application
For pumping heat transfer oil in closed industrial circulation systems
 
Special features/product advantages
  • Self-cooled mechanical seal, independent of direction of rotation
  • Great variety of applications due to a wide fluid temperature range without additional wearing parts
Technical data
  • Permissible temperature range ‐10 °C to +350 °C at max. 9 bar
  • Mains connection 3~400 V, 50 Hz (others on request)
  • Protection class IP 55
  • Nominal diameter DN 20 to DN 80
WILO VEROTWIN DPL

WILO VEROTWIN DPL

Application
Pumping of heating water (acc. to VDI 2035), cold water and water/glycol mixtures without abrasive substances in heating, cold water and cooling systems.
 
Special features/product advantages
  • Reduction of space required and installation costs due to double pump design
  • Main/standby mode or peak-load operation (by means of external auxiliary device)
  • High standard of corrosion protection thanks to cataphoretic coating
  • Series design: motor with one-piece shaft
  • Version N: standard motor B5 or V1 with stainless steel plug shaft
Technical data
  • Minimum Efficiency Index (MEI) ≥ 0.4
  • Permissible temperature range -20 °C to +120 °C
  • Mains connection 3~400 V, 50 Hz (others on request)
  • Protection class IP 55
  • Nominal diameter DN 32 to DN 100
  • Max. operating pressure 10 bar (special version: 16 bar)